General specifications
|
Switching function
|
Normally open (NO)
|
Output type
|
PNP
|
Rated operating distance
|
40 mm
|
Installation
|
non-flush
|
Output polarity
|
DC
|
Assured operating distance
|
0 ... 32.4 mm
|
Actual operating distance
|
36 ... 44 mm typ. 40 mm
|
Reduction factor rAl
|
0.33
|
Reduction factor rCu
|
0.31
|
Reduction factor r304
|
0.74
|
Reduction factor rBrass
|
0.38
|
Output type
|
3-wire
|
Nominal ratings
|
Operating voltage
|
10 ... 30 V DC
|
Switching frequency
|
0 ... 180 Hz
|
Hysteresis
|
typ. 5 %
|
Reverse polarity protection
|
reverse polarity protected
|
Short-circuit protection
|
pulsing
|
Voltage drop
|
≤ 2 V
|
Operating current
|
0 ... 200 mA
|
Off-state current
|
0 ... 0.5 mA
|
No-load supply current
|
≤ 20 mA
|
Time delay before availability
|
80 ms
|
Operating voltage indicator
|
LED, green
|
Switching state indicator
|
LED, yellow
|
Functional safety related parameters
|
MTTFd
|
1057 a
|
Mission Time (TM)
|
20 a
|
Diagnostic Coverage (DC)
|
0 %
|
Compliance with standards and directives
|
Standard conformity
|
|
|
Standards
|
EN IEC 60947-5-2
|
Approvals and certificates
|
IECEx approval
|
|
|
Equipment protection level Gc (ec)
|
IECEx TUR 21.0019X
|
|
Equipment protection level Dc (tc)
|
IECEx TUR 21.0020X
|
ATEX approval
|
|
|
Equipment protection level Gc (ec)
|
TÜV 20 ATEX 8525 X
|
|
Equipment protection level Dc (tc)
|
TÜV 20 ATEX 8526 X
|
UL approval
|
cULus Listed, General Purpose
|
Marine approval
|
DNVGL TAA0000160
|
Ambient conditions
|
Ambient temperature
|
-25 ... 85 °C (-13 ... 185 °F)
|
Storage temperature
|
-40 ... 85 °C (-40 ... 185 °F)
|
Mechanical specifications
|
Connection type
|
Connector plug M12 x 1 , 4-pin
|
Housing material
|
PA
|
Sensing face
|
PA
|
Degree of protection
|
IP69K
|
Cable
|
|
|
Cable diameter
|
3.3 mm ± 0.15 mm
|
Mass
|
130 g
|
Dimensions
|
|
|
Height
|
40 mm
|
|
Width
|
40 mm
|
|
Length
|
67 mm
|
General information
|
Use in the hazardous area
|
see instruction manuals
|